479 East 186th Street Bronx, N.Y.  10458

Monday - Friday 7am-5pm 


Price: $240.00

    Quantity:
    Item #: L8148A1017
    Availability: In stock
    In stock Quantity: 2

    Overview

    Immersion-type controllers that combine high limit protection with switching relay control of burner and circulator motors.

    Features

    • High limit opens burner circuit only.
    • Select models include transformer and accessory terminals for adding a remote low limit controller.
    • Case available for horizontal or vertical mounting.
    • Requires a 24 Vac thermostat with heat anticipator set at 0.2A.
    • TRADELINE models include well adapter, tube of heat conductive compound and range stops..

    Product Specifications

    Hazmat Information
    UN 1294, TOLUENE, 3, II
    Application
    High Limit
    Dimensions (in.)
    4 5/16 in. high x 6 1/8 in. wide x 3 1/8 in. deep
    Dimensions (mm)
    110 mm high x 156 mm wide x 79 mm deep
    Maximum Safe Operating Pressure (psi)
    Immersion Well: 255 psi
    Maximum Safe Operating Pressure (kPa)
    Immersion Well: 1757 kPa
    Temperature Range (F)
    Maximum--150 F with 1.2 A 24 V load; 77 F with 1.4 A 24 V load
    Temperature Range (C)
    Maximum--66 C with 1.2 A 24 V load; 25 C with 1.4 A 24 V load
    Mounting
    Horizontal
    Frequency
    60 Hz
    Approvals, Underwriters Laboratories Inc.
    UL Listed: File No. MP466, Vol. 13, Sec. 2, Guide No. MBPR2.
    Approvals, Canadian Standards Association
    Certified: File No. LR1620, Guide No. 400-E-O
    Tradeline Value
    Tradeline
    Electrical Connections
    Quick-Connect / Screw
    Operating Humidity Range (% RH)
    0 to 95% RH, non-condensing
    Voltage
    120 Vac
    Operating Temperature Range (F)
    High Limit-- 140 F to 240 F
    Operating Temperature Range (C)
    High Limit-- 60 C to 116 C
    Differential Temperature (F)
    8 F fixed
    Switching Action
    SPST: High Limit & Circulator
    Anticipator Setting
    0.2 A
    Capillary Length (in.)
    4 1/2 in.
    Insulation Depth (in.)
    1 1/2 in. to 3 in. less well
    Insulation Depth (mm)
    38 mm to 76 mm less well
    Capillary Length (mm)
    114 mm
    Electrical Ratings, Burner
    At Full Load-- Low Voltage: 0.8 A max. @ 24 Vac: Line Voltage: 7.4 A @ 120 Vac: 3.7 A @ 240 Vac; At Locked Rotor-- Line Voltage: 44.4 A @ 120 Vac: 22.7 A @ 240 Vac
    Electrical Ratings, Circulator
    At Full Load-- 7.4 A @ 120 Vac: 3.7 A @ 240 Vac; At Locked Rotor-- 44.4 A @ 120 Vac: 22.2 A @ 240 Vac