    Overview

    Provide electronic control of direct spark ignition systems, with external spark transformers, used on gas-fired furnaces, boilers, conversion burners and other heating appliances.

    Features

    • Controls ignition sequence and gas control operation in direct spark ignition systems.
    • Control separate 120 Vac spark generator that provides high voltage potential for main burner ignition.
    • Lockout after one trial for ignition if main burner fails to ignite.
    • Reset from thermostat after lockout. Use separate electrodes for spark ignition and flame sensing.
    • Use any 24 Vac combination gas control designed for direct spark applications and rated at 2.0A or less.

    Product Specifications

    Dimensions (in.)
    5 1/4 in. high x 4 1/16 in. wide x 1 15/16 in. long
    Dimensions (mm)
    133 mm high x 103 mm wide x 49 mm deep
    Electrical Ratings
    24 Vac
    Frequency
    60 Hz
    Approvals, Canadian Standards Association
    Design Certified
    Flame Failure Response Time (sec)
    2.0 sec. @ 2.5 microamp
    Ambient Temperature Range (F)
    -40 F to +175 F
    Ambient Temperature Range (C)
    -40 C to +79 C
    Ignition System Type
    Direct Spark Ignition
    Ignition Sequence
    Single trial for main burner ignition (then shut down and lockout)
    Typical Gas Control
    VR8205, VR8305
    Type of Gas
    Natural or LP
    Flame Sense
    Two Rod
    Ignition Source
    External (120 VAC powered) High Voltage Spark Generator
    Ignition Trials To Lockout
    1
    Lockout Timing
    4 sec.
    Ignition Trial Time (sec)
    4 sec.
    Maximum Valve Load @ 24 Vac (Amps)
    2A
    Flame Failure Re-ignition Time (sec)
    0.8 sec. maximum