Use with V5055 or V5097 Gas Valves to control gas supply for commercial and industrial burners. Valve opens to low fire position when power is applied; valve opens all the way on demand.
Features
- Provide final safety shutoff service when used with V5055 or V5097 gas valve.
- One-second maximum closing time.
- Continuously displays the valve position with a red indicator when open and a yellow indicator when closed.
- Mount in any position directly to valve bonnet with three setscrews.
- Provide final safety shutoff service when used with V5055 or V5097 Gas Valves.
Maximum Safe Operating Pressure (psi)5 psiMaximum Safe Operating Pressure (kPa)34 kPaTemperature Range (F)-40 F to +150 FTemperature Range (C)-40 C to +66 CIncludesDamper ShaftUsed WithV5034; V5055; V5097; VE5000Electrical Ratings120 VacFrequency60 HzApprovals, Underwriters Laboratories Inc.When used with V5055A-E (3/4 to 4 in.) or V5097A-E (3/4 to 3 in.): Listed, File No. MH1639 Guide No. YIOZApprovals, Canadian Standards AssociationWhen used with V5055 and V5097: Certified General listed File No. 158158, Class 3371 for USA and CanadaApprovals, Swiss REWhen used with V5055 or V5097: AcceptableTimingOpening-- 13 sec; Closing-- < 1 secInternal Auxiliary SwitchNo