Universal 24 Vac, Standard Opening, Intermittent / Direct Ignition Gas Valve 3/4 x 3/4". Set 3.5" WC
These valves offers wide-capacity control for almost any IP, HSI or DSI gas-fired appliances.
Product Specifications
- Application
- Single Stage
- Dimensions (in.)
- 5 3/8 in. high x 4 1/16 in. wide x 2 11/16 in. deep
- Dimensions (mm)
- 135 mm high x 104 mm wide x 69 mm deep
- Includes
- Two 3/4 x 1/2 in. reducer bushings; Natural to LP Conversion Kit
- Item Type
- Product
- Mounting
- 0 to 90 degrees in any direction from the upright position of the gas control knob, including vertically.
- Frequency
- 50 Hz; 60 Hz
- Approvals, Underwriters Laboratories Inc.
- UL Component Recognized MCCZ2.MH5323
- Approvals, CSA
- CSA International: 112395
- Tradeline Value
- Universal
- Electrical Connections
- 1/4 in. quick-connect male terminals
- Voltage
- 24 Vac
- Operating Temperature Range (F)
- -40 F to +175 F
- Operating Temperature Range (C)
- -40 C to +79 C
- Approvals, Canadian Gas Association
- Body Pattern
- Straight-through
- Opening Characteristics
- Standard
- Pressure Ratings (psi)
- 1/2 psi
- Pressure Ratings (kPa)
- 3.5 kPa
- Inlet/Outlet Size (in.)
- 3/4 in. x 3/4 in.
- Pilot Gas Outlet
- Compression fitting for 1/4 in. OD tubing
- Pressure Tapping
- 1/8 in. NPT with plug
- Approvals, American Gas Association
- Type of Fuel
- Natural (LP with included conversion kit)
- Capacity (kBtuh)
- At 1 in. wc p.d.-- 300,000 BTUh: 30,000 BTUh minimum: 415,000 BTUh maximum Natural Gas
- Pressure Regulator
- Standard
- Pressure Regulator Setpoint (in. wc)
- 3.5 in. wc
- Pressure Regulator Setpoint (kPa)
- 0.87 kPa
- Ignition Type
- Direct Ignition; Intermittent Pilot