479 East 186th Street Bronx, N.Y.  10458

Monday - Friday 7am-5pm 


Price: $105.00

    Quantity:
    Item #: RA832A1066
    Availability: In stock
    In stock Quantity: 10

    Provide intermediate switching of a line voltage device from a low voltage controller.

    Features

    • Integral transformer provides low voltage power for control circuit.
    • The RA832A is a TPST relay. One relay pole is designed for low voltage or millivoltage (Powerpile) auxiliary load. Two other relay poles are for line voltage loads.

    Product Specifications

    Application
    Provide intermediate DPST switching of a line voltage device from a low voltage controller.
    Dimensions (in.)
    5 1/4 in. high x 4 1/4 in. wide x 2 5/16 in. deep
    Dimensions (mm)
    133 mm high x 108 mm wide x 59 mm deep
    Includes
    Integral transformer, enclosure
    Item Type
    Product
    Electrical Ratings
    Maximum Input-5.0 W
    Frequency
    50 Hz; 60 Hz
    Approvals, Underwriters Laboratories Inc.
    Listed: File No. E4436, Guide No. XAPX
    Approvals, CSA
    Certified: File No. LR1620
    Tradeline Value
    Tradeline
    Electrical Connections
    Control Circuit- 2-Wire
    Temperature Ratings (C)
    46 C maximum ambient for 60 Hz. 41 C maximum ambient for 50 Hz.
    Temperature Ratings (F)
    115 F maximum ambient for 60 Hz. 105 F Max. Ambient for 50 Hz.
    Switching
    DPST; one pole line voltage, the other low voltage or millivolt
    Pilot Duty Ratings
    Secondary-- 50 VA @ 24V
    Contact Ratings (AFL)
    At 120 Vac-- 7.4A AFL; 240 Vac-- 3.7A
    Contact Ratings (ALR)
    At 120 Vac-- 44.4A; 240 Vac-- 22.2A
    Contact Ratings (resistive)
    At 120 Vac-- 10A; 240 Vac-- 6.0A
    Input Voltage
    120V
    Coil Ratings Voltage
    24 Vac
    Coil Ratings Current
    0.4A
    Electrical Ratings, Contacts
    Maximum connected load is 2000 VA (120 Vac to 240 Vac); Secondary DC Rating-- 1A @ 12 Vdc; Secondary millivolt Rating-- 300 mA min. @ 750 mV