Honeywell Electronic Gas valve Retrofit Kit. Includes V8304M 3/4" x 1/2" or 3/4" Electronic Gas valve, S8610U3009 Ignition Module, Ignition Cable & Wiring Harness.
Intermittent Pilot Retrofit Kits save energy by converting atmospheric standing pilot systems to intermittent pilot. Typical applications are gas-fired atmospheric furnaces, boilers and heating appliances.
Features
- Use with natural or LP gas
- Includes gas valve, ignition module, pilot burner hardware, ignition cable, and wiring harness
- Provides 100 percent pilot gas shutoff if pilot fails to light; after 6-minute delay, trial for ignition is repeated.
- Ignition trail/delay sequence is repeated until the appliance lights or call for heat is removed..
Product Specifications
Dimensions (in.)3 15/16 in. high x 5 7/16 in. wide x 2 5/8 in. deepDimensions (mm)100 mm high x 138 mm wide x 67 mm deepIncludesVR8304M3558 (1/2 x 3/4; 3.5" setting; 270kBtu/hr at 1 in. p.d.)Electrical Ratings24 VacFrequency60 HzFlame Failure Response Time (sec)2.0 secPrePurge0 or 30 secondsAmbient Temperature Range (F)-40 F to +165 FAmbient Temperature Range (C)-40 C to +74 CIgnition System TypeIntermittent PilotIgnition SequenceContinuous retry, after trial for ignition, pilot gas shuts off for 5 minutes, then another trial for pilot ignition takes placeTypical Gas ControlVR8204, VR8304Type of GasNatural or LPFlame SenseSingle Rod or Two RodsIgnition SourceInternal high voltage spark generatorIgnition Trials To Lockoutcontinuous retryLockout Timing15 or 90 secondsIgnition Trial Time (sec)15 or 90 secondsMaximum Valve Load @ 24 Vac (Amps)1A Pilot, 2A Main @ 24VacTypical Ignition Hardware