TECHNICAL DATA
Mounting Flange mounting, any position
Connection threads Inlet Nozzle outlet Pressure gauge port Bleeder valve port
1/4 NPTF 1/8 NPTF 1/8 NPTF 1/8 NPTF
Valve function Pressure regulation
Cut-off Diaphragm
Strainer 7 GHP
Shaft 5/16 in
By-pass plug Not inserted in return port, for one pipe system. To be inserted in return port with a 5/32 Allen key for two-pipe system.
General
Nozzle pressure range 100 - 200 psi
Delivery pressure setting 100 psi
Rated nozzle flow 7 GPH @100 psi, 3450 rpm 3 GPH @200 psi, 3450 rpm
Oil temperature 50 - 115 F
Inlet and return pressures 10 psi max. NFPA limits pressures to 3 psi max
Suction height Single pipe : 6" Hg max. vacuum, Two-pipe : 12" Hg max. vacuum, to prevent air separation from oil
Power consumption 80 W @100 psi 125 W @150 psi
Rated speed 3450 rpm max.